Customization: | Available |
---|---|
Type: | Universal Testing Machine |
Accuracy Grade: | 1 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
CT (protection, measurement) | PT |
Voltage current characteristic curve (excitation characteristic) | Voltage current characteristic curve (excitation characteristic) |
Auto calculate knee point value | Auto calculate knee point value |
Auto display 5% and 10% error curves | Turns ratio measurement |
Turns ratio measurement (6 channels simultaneously) | Polarity determination |
Differential measurement | Differential measurement |
Phase measurement (angular difference) | Phase measurement (angular difference) |
Polarity judgment | AC withstand voltage test |
Primary current injection test | Second burden measurement |
AC withstand voltage test | Secondary winding resistance test |
Secondary burden test | |
Secondary winding resistance test | |
Comprehensive CT test (one-time wiring test for voltage current turns ratio) |
Item | Parameter | |
Power supply | AC220V±10%, 50Hz | |
Output | 0-3000Vrms, 2Arms(20A peak) | |
Output current | 0-1000A | |
Accuracy of excitation | ≤0.5%(0.2%*the reading+0.3%*range) | |
Secondary winding resistance measurement | Range | 0.1~300Ω |
Accuracy | ≤1.0%(0.4%*the reading+0.6%*range) | |
Secondary actual burden measurement | Range | 5-500VA |
Accuracy | ≤0.5%(0.2%*the reading+0.3%*range) ±0.1VA | |
Accuracy of angular error | Accuracy | 4min |
Resolution | 0.1min | |
Accuracy of ratio error | 0.05% | |
CT ratio measurement | Range | ≤25000A/5A (5000A/1A) |
Accuracy | ≤0.5% | |
PT ratio measurement | Range | ≤500KV |
Accuracy | ≤0.5% | |
Operation environment | Temperature: -10ºC-40ºC, Humidity: ≤90%, Altitude: ≤1000m | |
Dimension &Weight | Dimension: 410mm × 260mm × 340mm Weight: ≤22Kg |