HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer

Product Details
Customization: Available
Accuracy Grade: 0.5
Load Way: Electronic Load
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO9001:2015, ISO14001:2015, ISO 45001:2018
Export Year
2011-07-01
  • HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
  • HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
  • HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
  • HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
  • HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
  • HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
Find Similar Products

Basic Info.

Model NO.
GDHG-106B
Display
Digital
Control
Computer Control
Weight
0-100Kg
Power Source
AC220V
Power Supply
AC220V±10%, 50Hz
Output Current
0-1000A
Accuracy of Excitation
≤0.5%(0.2%*The Reading+0.3%*Range)
Accuracy of Angular Error
4min
Accuracy of Ratio Error
0.05%
Dimension&Weight
440mm* 340mm* 380mm; 35kg
Data storage
3000 grups
Output voltage
0-2500Vrms, 5Arms(20A peak)
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan China
HS Code
9030841000
Production Capacity
2000PCS/Year

Product Description

GDHG-106B Current Transformer and Voltage Transformer Analyzer

HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer

General introduction

GDHG-106B is a multifunctional tool specially designed for analyzing current transformers and voltage transformers of protection or measurement use. The operator only needs to set values for test current and voltage, the instrument will automatically boost voltage and current, and then show test results in a short time. Test data can be saved, printed, and uploaded to PC through USB interface.


Features

1. Finish all testing subject by itself, no need to connect auxiliary equipment.

2. Built-in printer, to print results easily.

3. Large screen LCD, graphically display.

4. Auto display excitation knee point value, 5% and 10% error curve.

5. Save 3000 groups data.

6. With USB port. The data can be saved in USB disk and read by PC(WORD format file).

7. Portable design about 35kg, suitable for on-site test.

8. Engineering plastic box with damping, strong and reliable.



Specifications

Main functions
CT (protection type, metering type)  PT
  1. Voltage current characteristic curve (excitation characteristic) 
  1. Voltage current characteristic curve (excitation characteristic)
  1. Auto calculate knee point value
  1. Auto calculate knee point value
  1. Auto display 5% and 10% error curve
  1. Turns ratio measurement
  1. Turns ratio measurement
  1. Polarity determination
  1. Ratio error measurement
  1. Ratio error measurement
  1. Phase measurement (angular difference)
  1. Phase measurement (angular difference)
  1. Polarity determination 
  1. AC withstand test
  1. Primary current injection test
  1. Secondary winding resistance measurement
  1. AC withstand test
  1. Secondary burden measurement
  1. Secondary winding resistance measurement
 
  1. Secondary burden measurement
 
  1. Fast Test (Iron core demagnetization comprehensive test, complete excitation, ratio and polarity test at one time)
 

Main parameters 
Item Parameter
Power supply AC220V±10%, 50Hz
Output 0-2500Vrms, 5Arms (20A peak)
Output current 0-1000A
Accuracy of excitation ≤0.5%(0.2% of the reading+0.3% of the range)
Secondary winding resistance measurement Range 0.1-30
Accuracy 1.0% (0.4% of the reading+0.6% of the range)
Secondary actual burden measurement Range 5-500VA
Accuracy ≤0.5% (0.2% of the reading+0.3% of the range) ±0.1VA
Angular error measurement Accuracy 4min
Resolution 0.1min
CT ratio measurement Range 25000A/5A (5000A/1A)  
Accuracy ≤0.5% (0.2% of the reading+0.3% of the range)
PT ratio measurement Range 500KV
Accuracy ≤0.5% (0.2% of the reading+0.3% of the range)
Operation environment Temperature: -10ºC-40ºC, Humidity: ≤90%, Altitude: ≤1000m
Dimension & Weight Dimension: 345mm × 445mm × 380mm   
Weight: about 30kg




HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer
HVHIPOT GDHG-106B Current Transformer and Voltage Transformer Analyzer




 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier