Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General Information
Partial discharge is one of the common reason of medium and high voltage equipment and cable insulation failures. Partial discharge testing can detect harmful defects and help identify potential future failures.
The GD-610C remote ultrasonic partial discharge detector uses an ultrasonic spectrum probe (sensor) to collect ultrasonic signals and analyze the signal to diagnose the charged detection, it is a diagnosis device for the accident of the distribution line.
The device determines the line position and the fault type of the faulty hidden line when it is live. After collecting the ultrasonic abnormal signal, it transmits signals to the host, converts it into an audible sound signal and waveform, and finally diagnoses the type of the hidden danger and grade by the analysis software. It helps inspection personnel to accurately discover the hidden troubles of the line faults and prevent the occurrence of major accidents, and avoid unnecessary power outages.
Features
Specifications
Software | |
System | Android 8.0.0 |
Memory | 4.0GB |
Function | data display, chart display |
Storage | 64GB |
Take Photo | support |
Ultrasonic sensor | |
Measurement range | -7dB~60dB |
Resolution | 1dB |
Accuracy | ±1dB |
Sensitivity | -65dB |
Sensor center frequency | 40.0±1.0KHz |
Sensor bandwidth | 2.0KHz |
Battery | |
Built-in battery | Lithium battery, 8.4V, 3500mAh |
Use time | About 8 hours |
Charging time | Approx. 5 hours |
Battery protection | Over voltage and over current protection |
Battery charger | |
Rated voltage | 8.4V |
Charging output current | 2A |
Working temperature | -20ºC-60 ºC |
Working humidity | <80% |
Hardware | |
Housing | Monochrome molding plastic |
Screen | Wireless display (Android phone or tablet) |
Control | Start/stop button |
Interface | Charger interface; headphone interface; |
Headphones | High fidelity noise reduction wired headset; wireless Bluetooth headset |
Size | Instrument size: 380mm * 30mm Instrument box size: 395mm * 295mm * 105mm |
Weight | Instrument weight: 0.5KG Instrument with box weight: 2.3KG The weight of whole set of equipment: 2.7KG |
Working environment | Operating temperature: -20 ºC ~ 50 ºC Ambient humidity: 0-90%RH IP rating: 54 |