SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis

  • Audited Supplier
  • 16 yrs

Contact Supplier

Product Highlights

  • High Precision Sensors: Uses Finland Vaisala DRYCAP sensors for superior dew point measurement accuracy.
  • Portable Design: Compact chassis with carrying handle, weighing only 2kg for easy field transport.
  • Dual Power Supply: Supports AC and DC power with high-power lithium battery lasting over 8 hours.
  • Multi-Function Analysis: Simultaneously measures SF6 humidity, purity, and decomposition products (H2S, SO2).
  • No Preheat Required: Advanced algorithms allow immediate startup testing without warm-up or oscillation.
  • Large Data Storage: Built-in memory stores up to 1000 sets of test data for convenient record keeping.
  • Leak-Proof Design: Miniature self-sealing joints prevent gas leakage when the air path is disconnected.
  • Anti-Interference Circuit: Special circuit design ensures product reliability against electromagnetic interference.

Product Images of SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis

SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis pictures & photos
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis pictures & photos
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis pictures & photos
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis pictures & photos
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
  • SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
  • SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
    SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
  • SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
    SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
  • SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
    SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
  • SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
    SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis

Find Similar Products

Product Description

SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis

GDSF-311WPD is ideal instrument when it is necessary to test water content, purity and decomposition products of SF6 gas. The core component of dew point test is DRYCAP series sensors produced by Finland Vaisala company. With professional hardware chips and excellent software algorithms of STMicroelectronics, we have produced a new generation of gas moisture test instrument.

Application

Moisture monitoring of SF6 gas electrical equipment for electric power
SF6 gas cylinder gas quality test
High purity gas manufacturing
Semiconductor industry dry gas supply
Research and development use
Clean room/dry house monitoring
Metal heat treatment site and laboratory industrial gas humidity detection, such as air, CO2, N2, H2, O2, SF6, He, Ar and other inert gases.



Features
  1. Better than ±1ºC measurement accuracy.
  2. All gas path with high polymer material design, ensures no water wall hanging phenomenon and guarantees the test speed.
  3. The oil-free stainless-steel body regulating valve is used to ensure the accuracy of the measured value.
  4. Advanced software algorithms improve the test accuracy of sensors.
  5. Combined chassis configuration solution, users can easily combine related instruments and accessories. The overall package is carried, which makes the user have a more relaxed experience.
  6. Startup test, no need to preheat and oscillate.
  7. Temperature conversion and pressure data correction.
  8. Fuzzy computing technology.
  9. High-power lithium battery power, realize AC and DC dual power supply. No on-site AC power is required. Lithium battery power supply continues to work for more than 8 hours without the need of an external power supply.
  10. Anti-electromagnetic interference circuit design to ensure product reliability.
  11. Large-capacity memory, which can realize 1000 sets of data storage functions.
  12. The test data is stable and can provide both standard dew point values and converted dew point values at 20ºC.
  13. The best test flow area shows that the user can adjust the gas flow intuitively and quickly. Reduce test time.
  14. The air inlet is designed with a miniature self-sealing joint, and the air path to be tested will not leak when the air path is disconnected.


Specifications

SF6 Humidity

Measurement method

 Resistive and Capacitive measurement principle

Measurement range

 dew point -80ºC--+20ºC(support ppmv)

Accuracy

 ±1ºC

(when the dew point temperature is below 0 ºC, the sensor output is the frost point)

Response time

 63% [90%]

+20→-20ºC Td 5s[45s]

-20→-60ºC Td 10s[240s]

Resolution

 0.01ºC

Repeatability

 ± 0.5 ºC

Display unit

 ºC, ppm, ºCP20(converted value at 20ºC)

Gas flow

 400-600ml/min

Flow display

 0-1000mL digital flow meter

Sample gas pressure

 ≤1MPa

SF6 Purity

Measurement method

 TCD technology.

Measuring range

 0 ~ 100% SF6.

Accuracy and repeatability

 ± 0.5%, nothing to do with the flow.

SF6 decomposition products

H2S

1 ~ 200ppm (standard)

SO2 1 ~ 100ppm (standard).
Sensitivity 0.5ppm
Gas flow  0.5±0.1L/min
Other features

Power supply

 220VAC±10%, 50Hz, AC/DC use, over-charge protection, continuous working is no lower than 8hours.

Use environment temperature

 -20--+60ºC

Environment humidity

 90%RH

Measurement value influence

 No effect of pressure and flow

Dimension

 395*295*155mm

Weight

 about 2kg


SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis
SF6 Gas Multi-Analyzer dew point purity and SO2 H2S content analysis

About the Supplier

This supplier has been audited by TÜV Rheinland. Verify the report on the official TÜV Rheinland website with ID "MIC-ASR249016". Items marked "verified" are certified.

Watch Video
Watch Video
HV Hipot Electric Co., Ltd.
HV Hipot Electric Co., Ltd.
HV Hipot Electric Co., Ltd.
HV Hipot Electric Co., Ltd.
HV Hipot Electric Co., Ltd.
HV Hipot Electric Co., Ltd.
HV Hipot Electric Co., Ltd.
HV Hipot Electric Co., Ltd.

About Our Factory & Business Background

verified Business Type
Manufacturer/Factory & Trading Company
Address
Building A1-3, Kechuang Center, Chuanggu Road, Dongxihu District, Wuhan, Hubei, China
verified Plant Area
2712 square meters
verified Number of Employees
68
verified Registered Capital
31,130,000 RMB
verified Terms of Payment
LC, T/T
verified International Commercial Terms(Incoterms)
FOB, CIF, CFR
verified Average Lead Time
Peak Season Lead Time: one month
Off Season Lead Time: one month
verified Nearest Port
Wuhan Port

Our Production Capability & Technical Expertise

verified Main Products
Transformer Testers, Partial Discharge Test System, Insulation Tester, High Voltage Test Set, Switchgears Test Set
verified ODM Service Available
Yes
verified R&D Engineers
8 people
verified Own Brand
Yes

Our Industry Experience & Global Business Record

verified Year of Establishment
2006-11-08
Export Year
2011-07-01
verified Main Markets
North America, South America, Southeast Asia/ Mideast, Africa, East Asia(Japan/ South Korea), Australia
verified Annual Export Revenue
6,000,000 RMB
verified Number of Foreign Trading Staff
5
verified Overseas Agent/Branch
No

FAQ

How long does the battery last on a single charge?
The high-power lithium battery allows continuous operation for more than 8 hours without external power.
Can this device measure SF6 purity and decomposition products?
Yes, it measures SF6 purity (0-100%) and decomposition products including H2S (1-200ppm) and SO2 (1-100ppm).
Does the instrument require preheating before use?
No, the device features advanced software algorithms that allow for immediate startup testing without preheating.
What is the data storage capacity of the analyzer?
The device has large-capacity memory capable of storing up to 1000 sets of test data.
Is the device portable and easy to carry?
Yes, it features a combined chassis design with an overall carrying package, weighing approximately 2kg.
What sensors are used for the dew point measurement?
The core component uses DRYCAP series sensors produced by Finland's Vaisala company.

Send your message to this supplier

Contact Information
Recipient
Message

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now