Product Description
It's used to generate HV impulse when using impulse flashover method to detect high impedance fault.
Features
- Strong burning ability, max.burning power is 1000W, breakdown point can be burned in short time and the resistance of breakdown point is decreased.
- If working together with GD-4133 Cable Fault Tester, there are two locating ways:
a.Low voltage pulse: If only using GD-4133, open circuit and low impedance grounding faults of cable can be located, and the length of cable can be measured or wave speed of cable can be detected.
b. High voltage flashover: The discharging pulse voltage waveform of fault point is sampled by discharging sphere gap, which can locate fault distance.
- Generate impulse of fixed frequency. If working together with GD-4132 Cable Fault Locator, there are following functions:
a. Audio frequency: locate high impedance, flash-over faults.
b. To pinpoint cable's route, identify special cable.
c. To metallic breakdown(dead grounding), using magnetic-field measurement to locate accurately.
- It also can be used in DC HV withstand test.
Specifications
Input power supply |
AC220V, 50Hz |
Output voltage |
DC 0-32kV (adjustable) |
Rated power |
2kVA |
Max. energy |
2048J, 4uF |
DC flashover voltage |
32kV |
DC flashover current |
63mA |
Max. impulse current |
500mA |
Discharging method |
DC HV, one time, cycle |
Cycle discharging time |
3-6 seconds |
Environmental temperature |
0-40ºC |
Humidity |
<75% RH |
Altitude |
<1000m |
Insulation level |
A |
Dimension |
430*540*410mm |
Weght |
About 31kg |