Customization: | Available |
---|---|
After-sales Service: | YES |
Warranty: | 1 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Voltage Range |
30V~480V |
5A Terminal |
Active Energy , Active Power |
±0.05% ±0.1% |
||||
Voltage Error |
±0.1% |
Reactive Energy, Reactive Power |
±0.2% |
|||||
Current Range
|
Terminal |
0.1-5A |
Current |
±0.1% |
||||
5A Clamp Meter |
Active Energy , Active Power |
±0.2% ±0.5% |
||||||
Clamp Meter |
500A |
Reactive Energy, Reactive Power |
±0.2% ±0.5% |
|||||
Current |
±0.2% ±0.5% |
|||||||
Input Frequency Range |
45-55Hz |
Self-check Current |
5A |
|||||
Frequency Measurement Error |
±0.01Hz |
Self-check Error |
±0.1% |
|||||
Phase Measurement Range |
-180°~ +180° |
Current Clamp |
Active Energy , Active Power |
±0.2% ±0.5% |
||||
Max Phase Error |
±0.1° |
Reactive Energy, Reactive Power |
±0.2% ±0.5% |
|||||
Harmonics Measurement |
±0.1% |
Current |
±0.2% ±0.5% |
|||||
Harmonics Measurement Range |
2-21 times |
|||||||
Harmonic Power Measurment |
2-42 times |
Other |
Turn Ration Measurement |
±0.2% ±0.5% |
||||
Impulse Constant |
Low Frequency |
5A |
3600P/kWh |
Voltage Effect |
< ±0.01% |
|||
Other |
3600*(5/Ie)P/kWh |
Frequency Effect |
< ±0.01% |
|||||
High Frequency |
5A |
3.6x107 P/kWh |
Temperature Effect |
< ±0.005%/ºC |
||||
Other |
3.6x107 *(5/Ie) P/kWh |
Deterioration in 24 hours |
< ±0.01% |
|||||
Harmonics Effect |
< ±0.01% |
|||||||
|
Note:Ie--Rated Current |
Turn-on stabilization time
|
<3 min |
|||||
Power Supply |
AC 55V - 480V |
Temperature |
-25ºC- +45ºC |
|||||
Power Consumption |
< 10W |
Relatively Humidity |
40%-95% |
|||||
Dimension |
245*168* 67mm |
Weight |
1.5 kg |