Customization: | Available |
---|---|
After-sales Service: | yes |
Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated test voltage steps | GD3126A (5kV) | |||||
250V, 500V, 1.0kV, 2.5kV, 5.0kV | ||||||
Output voltage error | ±5% | |||||
Resistance range | Upper limit | 500GΩ~10TΩ | ||||
Lower limit | 0.1MΩ | |||||
Accuracy class | 5.0 class | |||||
High voltage display error | ±( 5%•Ux + 1d ) | |||||
Leakage current Ix measuring range & error | 0.1nA~9.9mA 5% | |||||
absorption capacitance Cx measuring range & error | 0.1pF~99uF 5% | |||||
Temperature measuring error | ±0.5ºC | |||||
Humidity measuring error | ±2%RH | |||||
Short circuit current | Approx. 3mA | |||||
Voltage ripple | <3% | |||||
Insulation resistance | > 500 MΩ (between test wire and case) | |||||
Withstand voltage | AC10.0kV 50Hz 1min (between test wire and case) | |||||
Power supply | 12V lithium battery | |||||
Battery service time after one charging | 30days 10times DAR & 5times PI test per day | |||||
Working temperature and humidity | 0ºC ~ + 40ºC < 85%RH | |||||
Storage temperature and humidity | - 20ºC ~ + 50ºC < 90%RH | |||||
Dimension (mm) | 325 (L)*250(W)*130(H) | |||||
Weight | 3.7kg | |||||
Resistance measuring error | ||||||
Voltage steps | 250 V | 500 V | 1.0 kV | 2.5 kV | 5.0 kV | |
±( 3%·Rx + 1d ) | 1GΩ | 2GΩ | 4GΩ | 10GΩ | 20GΩ | |
±( 5%·Rx + 1d ) | 10GΩ | 20GΩ | 40GΩ | 0.1TΩ | 0.2TΩ | |
±( 10%·Rx + 2d ) | 100GΩ | 200GΩ | 0.4TΩ | 1TΩ | 2 TΩ | |
±( 25%·Rx + 2d ) | 500GΩ | 1TΩ | 2TΩ | 5TΩ | 10TΩ |
Insulation resistance tester | 1 set |
Test connecting cable for L terminal (Red) | 1 root |
Test connecting cable for G terminal (Green) | 1 root |
Test connecting cable for E terminal (Black) | 1 root |
3APower adapter (For printer power supply and instrument charging) | 1 pc |
RS232 Serial communication line | 1 root |
User's guide | 1 copy |