Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Working condition | -15ºC~40ºC | RH<80% | ||||||
Anti-interference principle | Frequency conversion | |||||||
Power supply | AC 220V±10%, 50/60Hz | Generator can be used. | ||||||
High voltage output | AC 0.5KV~10KV (12kV optional) | Every 0.1kV | ||||||
Accuracy | 2% | |||||||
Max. current | 200mA | |||||||
Capacity | 2000VA | |||||||
Self-excitation power | AC 0V~50V/15A | 50Hz, 60Hz single frequency 45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic dual frequency |
||||||
Resolution | tgδ: 0.001% | Cx: 0.001pF | ||||||
Accuracy | tgδ: ±(reading*1.0%+0.040%) | |||||||
C x: ±(reading*1.0%+1.00PF) | ||||||||
Measurement range | tgδ | Without limit | ||||||
C x | 15pF < Cx < 300nF | |||||||
10KV | Cx < 60 nF | |||||||
5KV | Cx < 150 nF | |||||||
1KV | Cx < 300 nF | |||||||
CVT test | Cx < 300 nF | |||||||
LCR measurement range | L>20H(2kV) | R>10KΩ(2kV) | ||||||
LCR measurement accuracy | 0.1% | Resolution | 0.01 | |||||
CVT ratio range | 10~10000 | |||||||
CVT ratio accuracy | 0.1% | |||||||
CVT ratio resolution | 0.01 | |||||||
Insulation resistance | DC high voltage | 5~10kV | Accuracy | ±(2%*Reading +10V) | ||||
IR accuracy | 100kΩ-1000GΩ: <5% (test voltage not less than 250V) 100GΩ-1000GΩ: 10% (test voltage not less than 10000V) |
|||||||
Dimension | Main unit: 350(L)×270(W)×270(H) | |||||||
Accessory box: 350(L)×270(W)×160(H) | ||||||||
Memory capacity | 200 groups, USB flash disk storage is supported. | |||||||
Weight | Main unit: 22.75Kg | |||||||
Accessory box: 5.25Kg |