HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set

Product Details
Customization: Available
After-sales Service: yes
Function: Storage
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO9001:2015, ISO14001:2015, ISO 45001:2018
Export Year
2011-07-01
  • HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set
  • HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set
  • HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set
  • HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set
  • HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set
Find Similar Products

Basic Info.

Model NO.
GDAS-500
Display
Digital
Usage
Circuit Breaker
Type
Electrolytic Capacitor Leakage Current Tester
Environment
Low Temperature
Warranty
With Warranty
Power Source
DC 100V-300V
Weight
〉10Kg
Installation
Portable Precise
Customized
Customized
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
Hvhipot
Origin
China
HS Code
9030332000
Production Capacity
1000PCS/Year

Product Description


I. General Information  
HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set



Circuit Breakers are one of the critical "safety-valves" of electrical systems and basic maintenance procedures are essential to maintain maximum reliability.

According to the actual situation of the DC circuit breaker ampere-second characteristic test system, our company has introduced a DC circuit breaker ampere-second characteristic test system suitable for substation site use, easy to carry, and high degree of automation. It can provide DC protection for the operation and maintenance department. Characteristic testing methods are used to verify the action characteristics and level difference coordination of DC protection appliances, so as to improve the reliability of the DC system operation and ensure the safe and reliable operation of the power grid.



II. Features
 
  1. 320*240 LCD screen, thermal printer, interactive keyboard operation, and intelligent operation system.
  2. Power electronics controlling technique has been adopted to output high current, which is high speed, high precision and continuous adjustability.
  3. Current range can be automatically switched by multiple high precision sensors.14-digit AD acquisition chip of high capacity.
  4. Automatic data storage. Be capable of saving 200 testing results, which will not lose in power failure.
  5. Optional for ampere-second characteristic test (action test) or through current characteristic test (non-action test).
  6. Protection functions for overheat, over-current and over voltage. Anti-interference capacity and good EMC (electromagnetic compatibility).

III. Main Functions

According to National Standard, the DC circuit breaker should be made trip test.

1. Time-current Characteristic Test

A. Power on the breaker with 1.13In current (non-tripping current) till to required time, the breaker should not trip. Then increase the current to 1.45In (tripping current) within 5 seconds, the breaker should trip within required time.

B. Power on each level of the breaker with 2.55In current, break time > 1 second.
Break time < 60seconds when rated current of circuit breaker ≤ 63A.
Break time < 120seconds when rated current of circuit breaker > 63A.

2. Instantaneous Tripping Test
 
  1. B type Circuit Breaker: Power on each level of circuit breaker with 3In current, break time should be more than 0.1s.

Power on each level of circuit breaker with 5In current, break time should be less than 0.1s.

B. C type Circuit Breaker: Power on each level of circuit breaker with 5In current, break time should be more than 0.1s.
Power on each level of circuit breaker with 10In current, break time should be less than 0.1s.

C. D type Circuit Breaker: Power on each level of circuit breaker with 10In current, break time should be more than 0.1s.
Power on each level of circuit breaker with 50In current, break time should be less than 0.1s.
These two tests should be meets the specifications of time-current characteristic table.
 
Test item Type Test current Initial State Limit of tripping or non-tripping Expected Result
a B,C,D 1.31In Cold State t1h (In63A)
t2h (In>63A)
Not tripping
b B,C,D 1.45In Following with test of item a t<1h (In63A)
t<2h (In>63A)
Tripping
c B,C,D 2.55In Cold State t<1h (In63A)
t<2h (In>63A)
Not tripping
d B,C,D 3In, 5In, 10In Cold State 1s<t<60s (In63A)
1s<t<120s (In>63A)
Tripping
e B,C,D 5In, 10In, 50In Cold State T<0.1s  
Time-Current Action Characteristic Table

Note: 1) Current is stable and up to setting value within 5s.
     2) Cold State means test object (DC circuit breaker) is not connected before testing and making test under standard calibration temperature.

IV. Specifications
 
  1. Power supply: AC220V±20%, 50Hz±0.5Hz
  2. Testing current range: 5-500A
  3. Testing current ripple coefficient: < 1%
  4. Stability of output current: ≤ ±1%
  5. Time record range: 0.001s-1000s
  6. Minimum time resolution: 0.001s
  7. Environmental temperature: -20~50ºC.
  1. Size: 230mm (width)*450mm (height)*500mm(depth), include Including aluminum box, accessories 290mm (width) * 530mm (height) * 550mm (depth)
  2. Weight: about 12.5kg. Accessories 10kg
  3. Packing: aluminum alloy instrument box
  4. Do not need any protective measures, can be tested directly

HVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test SetHVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test SetHVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test SetHVHIPOT GDAS-500 Ampere-Second Characteristics Circuit Breaker Test Set






 