| Nominal voltage | ±300kV |
| Rated energy | 30kJ(5kJ/stage) |
| Impulse capacitance | 0.666µF |
| Number of Stage | 3 |
| Charging voltage per stage | ±100kV |
| Rated level capacitance | 2µF (each impulse capacitor 2µF at 100kV, total 3pcs) |
| Output voltage waveform | (Load capacitance is 300-3000pF) T1= 1.2µs±30%, T2=50µs±20%, peak voltage error≤3% standard lightning impulse voltage full wave. |
| Impulse voltage waveform parameters and error are accorded with national requirements of GB311.1 and GB16927.1 standard and IEC standard. | |
| Output Voltage Efficiency | Standard lightning wave ≥90% when load capacitance is below 1000pF, standard lightning wave ≥85% when load capacitance is below 2000pF |
| Locking range | level voltage is within the range of 20%-100% of rated voltage, positive and negative locking range no less than 25% |
| Out-of-control rate of synchronous discharge | <5% |
| Min. output voltage | ≥±10% of rated voltage |
| Instability of charging voltage | <±1.0% |
| Continuous time | Above 2/3 of rated voltage, continuous working when charge anddischarge once every 120s. Below 2/3 of rated voltage, continuous working when charge and discharge once every 60s. |