GDYT series Partial Discharge Test System is used for testing insulation level of various insulation materials, insulation structure and electrical products.It is also considered as PD power frequency source for transformers, CT/PTs, HV circuit breakers, coupling capacitors, bushings and other power equipment.
Picture | Name | Quantity | Function |
Hipot Test Control Table GDYD-100kVA/100kV | 1 piece | Controlling and voltage boosting for test object which boosted to the rated voltage. | |
PD-free Gas type transformer YDQW-100kVA/100kV | 1 piece | ||
Coupling capacitor OWF-1000pF/100kV | 1 piece | ||
Protective resistor GR 8kΩ/100kV | 1 piece | ||
Isolation filter LBQ-100kVA | 1 piece | Device of anti-interference caused by power supply. | |
Partial discharge detector GDJF-2008 | 1 piece | Detecting and displaying partial discharge capacity. |
Power supply | 380V±22V,50Hz |
Rated Capacity | 100kVA |
Output Voltage | 100kV, current: 1000mA |
Input Voltage | 380V, current: 263A |
Short-circuit impedance | ≤ 8% |
Operation time | 60mins@100% rated voltage and current. Continuous working@ 50% rated voltage and current. |
Wave form distortion rate | <5% when voltage regulator input voltage distortion rate <3%, within 10-100% rated voltage range. |
PD value | ≤8pC @ 100% rated voltage ≤5pC @ 80% rated voltage |